The main technical
characteristics of Hydroelectric Microplants
Hydroelectric Microplants
with propeller turbines
|
Parameters
|
HMP
type
|
|
|
HMP
-10Pr
|
HMP
-10Pr
|
HMP
-15Pr
|
HMP
-15Pr
|
HMP
-50Pr
|
|
1.Output, kW
|
0,6-4,0
|
2,2-10,0
|
1,3-5,0
|
3,5-15,0
|
7,0-50,0
|
|
2.Head, m
|
2,0-4,5
|
4,5-10,0
|
1,75-3,5
|
3,5-7,0
|
2,0-10,0
|
|
3.Discharge, m3/s
|
0,07-0,14
|
0,10-0,21
|
0,10-0,20
|
0,15-0,30
|
0,36-0,80
|
|
4.Speed of rotation, rpm
|
1000
|
1500
|
1000
|
1500
|
600,
750
|
|
5.Nominal voltage, V
|
230
|
230
|
230
|
230
|
230,400
|
|
6.Nominal frequency, Hz
|
50
|
50
|
50
|
50
|
50
|
Hydroelectric Microplants
with diagonal turbines
|
Parameters
|
HMP
type
|
|
|
HMP
20PrD
|
HMP
type 100K
|
HMP
type 200K
|
|
1.Output, kW
|
10 -
20
|
up to
100
|
up to
200
|
|
2.Head, m
|
8 - 18
|
40 -
250
|
|
3.Discharge, m3/s
|
0,08 -
0,17
|
0,015-0,046
|
0,015-0,013
|
|
4.Speed of rotation, rpm
|
1500
|
750;1000;1500
|
|
5.Nominal voltage, V
|
230,400
|
230,400
|
|
6.Nominal frequency, Hz
|
50
|
50
|
The main data of the
units for small HMP
Hydrounits with propeller type turbines
|
Parameters
|
Type
of unit
|
|
|
GA 1
|
GA 8
|
GA 13
|
Pr 15
|
Pr 30
|
|
1.Output, kW
|
100-330
|
150-1800
|
50-200
|
up to
130,0
|
up to
290,0
|
|
2.Head, m
|
3,5-9,0
|
6,0-22,0
|
2,0-5,0
|
2,0-12,0
|
4,0-18,0
|
|
3.Discharge, m3/s
|
2,3-6,2
|
2,5-11,0
|
2,3-5,0
|
0,44-1,5
|
0,38-1,1
|
|
4.Speed of rotation, rpm
|
200-360
|
300;
600
|
190-300
|
600;
750; 1000
|
750;
1000
|
|
5.Nominal voltage, V
|
400
|
400;
6000; 10000
|
400
|
230/400
|
230/400
|
|
6.Nominal frequency, Hz
|
50
|
50
|
50
|
50
|
50
|
Hydrounits with Francis type turbines
|
Parameters
|
Type
of unit
|
|
|
GÀ-2
|
GÀ-4
|
GA 9
|
GA 11
|
|
1.Output, kW
|
up to
950
|
550
|
3300
|
5600
|
|
2.Head, m
|
30-100
|
25-55
|
70-120
|
100-160
|
|
3.Discharge, m3/s
|
0,4-1,25
|
0,4-1,3
|
0,6-3,2
|
1,5
-4,0
|
|
4.Speed of rotation, rpm
|
1000;
1500
|
1000
|
600, 750;
1000
|
750, 1000
|
|
5.Nominal voltage, V
|
400;
6000
|
400;
6000
|
6000;
10000
|
6000;10000
|
|
6.Nominal frequency, Hz
|
50
|
50
|
50
|
50
|
Hydrounits with Pelton type turbines
|
Parameters
|
Type
of unit
|
|
|
GÀ-5
|
GÀ-10
|
|
1.Output, kW
|
145-620
|
290-3000
|
|
2.Head, m
|
150-250
|
200-450
|
|
3.Discharge, m3/s
|
0,17-0,32
|
0,19-0,90
|
|
4.Speed of rotation, rpm
|
500;600
|
600;750;1000
|
|
5.Nominal voltage, V
|
400;
6000
|
400;
6000; 10000
|
|
6.Nominal frequency, Hz
|
50
|
50
|
Completeness of delivery of the Hydroelectric Microplant
|
#
|
Denomination
|
Overall dimensions,mm
|
Mass
,kg
|
|
1.
|
HMP
Pr10
|
|
1.1.
1.2.
1.3.
|
Power Unit (turbine and generator)
Automatic Control device ACD 10
Water intake ( if necessary )
|
2000x700x650
1000x400x650
1000x750x600
|
250
70
50
|
|
2.
|
HMP
Pr50
|
|
2.1.
2.2.
2.3.
2.4.
2.5.
|
Power Unit
ACD 50
Excitation System
(ES-1)
Water intake
Ballaster :
- water cooled
- air cooled
|
3970õ1000õ740
900õ650õ1200
700õ600õ1800
1000õ900õ850
1200õ500õ500
( 370x980x1150 ) x 2
|
1600
150
80
100
110
190
|
Delivery completeness, weight of the hydro units
for small HPP
|
#
|
Denomination
|
Weight, kg
|
|
|
|
GA-1
|
GA-13
|
GA-8
|
GA-2
|
GA-4
|
GA-9
|
GA-11
|
GA-5
|
GA-10
|
|
1
|
Hydroturbine with
propeller runner
|
3980
|
3720
|
7000
|
---
|
---
|
---
|
---
|
---
|
---
|
|
2
|
Hydroturbine with
Francis runner
|
---
|
---
|
---
|
1300
|
1350
|
3300
|
4400
|
--
|
--
|
|
3
|
Hydroturbine with
Pelton runner
|
--
|
---
|
--
|
--
|
--
|
--
|
--
|
2200
|
5000
|
|
4
|
Angle gear
|
1430
|
---
|
--
|
--
|
--
|
--
|
--
|
--
|
--
|
|
5
|
Run-away device
|
1850
|
---
|
1850
|
175
|
175
|
370
|
370
|
--
|
--
|
|
6
|
Generator (depending
on capacity)
|
1320-2600
|
350-1300
|
2600-3400
|
2000-2600
|
1500-2400
|
3000-13000
|
5000-28000
|
2500-3900
|
10000-25000
|
|
7
|
Automatic control
system (ACS)
|
100
|
100
|
100
|
100
|
100
|
120
|
200
|
100
|
200
|
|
8
|
Draft tube
|
--
|
--
|
3100
|
400
|
400
|
600
|
700
|
--
|
--
|
Home
|